Limited Availability ›
This product has limited availability. Some accessories, replacement parts, or services may still be available when it is no longer available.
CR9058E 60 V Isolated Analog Input Module with CR9058EC

Overview

The CR9058E is a ±60-volt input module for the CR9000X and CR9000 measurement and control systems. The CR9058E has 10 differential inputs. Each channel has its own isolation ground, which can be used to connect a shielded cable. The CR9058E has an on-board resistance temperature detector (RTD) to provide a reference temperature measurement for thermocouple measurements. It ships with one CR9058EC Easy Connector Module.

Read More

Benefits and Features

  • CR9058EC disconnects sensors easily so CR9000X can be moved from location to location
  • Can be added to or removed from CR9000X to support changing measurement needs

Technical Description

The CR9058E is an I/O module for the CR9000X-series and CR9000-series dataloggers. It contains 10 isolated differential channels and an internal RTD. The differential channels are used to measure thermocouples or other devices that have a low level voltage output. Each channel has its own isolated ground for connecting a shielded cable, and its own 24-bit A/D converter that supplies input isolation for up to ±60 Vdc. An internal digital signal processor filters noise. The module's RTD typically provides the reference temperature for thermocouple measurements.

The CR9058E includes one CR9058EC easy connector module. Easy connector modules allow sensor wiring to remain connected while the input module’s measurement electronics and the rest of the datalogger system are used elsewhere. Additional CR9055ECs are purchased as a separate line item.

Images


Specifications

-NOTE- Additional specifications are listed in the CR9000X(C) Specifications Sheet.
Analog Channels 10 isolated differential
Analog Voltage Range ±60000 mV
Operating Temperature -40° to +70°C
Dimensions
  • 24.1 x 2.5 x 11.5 cm (9.5 x 1.0 x 4.5 in.) without EC
  • 24.1 x 2.5 x 16.3 cm (9.5 x 1.0 x 6.4 in.) with EC
Weight
  • 540 g (19.1 oz) for card and EC
  • 357 g (12.6 oz) for card only
  • 183 g (6.5 oz) for EC only

Gain Error

-40° to +50°C ±0.02% of reading
-40° to +70°C ±0.07% of reading

Offset Error

-40° to +50°C ±0.01% of FSR
-40° to +70°C ±0.01% of FSR

Measurement Resolution

±2 Vdc Range ±10 μV
20 Vdc Range ±100 μV
±60 Vdc Range ±300 μV

Typical Current Drain

Operating 360 mA
Standby 5 mA

Compatibility

Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.

Dataloggers

Product Compatible Note
CR1000 (retired)
CR200X (retired)
CR216X (retired)
CR3000
CR5000 (retired)
CR800 (retired)
CR850 (retired)
CR9000X (retired)

Listed Under

Privacy Policy Update

We've updated our privacy policy.  Learn More

Cookie Consent

Update your cookie preferences.  Update Cookie Preferences