LLAC4 4-Channel Low-Level AC-Conversion Module
Expands Capacity
Increases number of signals datalogger can monitor
weather applications supported water applications supported energy applications supported gas flux and turbulence applications supported infrastructure applications supported soil applications supported

Overview

The LLAC4 is a small peripheral that increases the number of low-level ac signals a datalogger can monitor. The LLAC4 is often used to measure up to four anemometers, and it is especially useful for wind profiling applications.

Read More

Benefits and Features

  • Ideal for applications that require high numbers of pulse channels, but fewer control ports, such as in wind prospecting

Technical Description

The LLAC4 enables four datalogger control ports to emulate pulse-counting channels by converting the low-level ac signals to logic levels read by the control ports.

Minimum AC Input Voltage versus Output Square Wave Frequency

Input Sine Wave
(mV RMS)
Output Range (Hz)
20 1.0 to 20
200 0.5 to 200
2000 0.3 to 10,000
5000 0.3 to 20,000

Images

Specifications

Function Increases the number of low-level ac signals that a data logger can monitor.
Number of Channels 4
Power 0.1 mA (@ 12 Vdc)
Input Hysteresis 16 mV (@ 1 Hz)
AC Coupling Removal of DC Offset ≤ ±0.5 V
Maximum AC Input Voltage ±20 V
Cable Length 0.6 m (2 ft)
Dimensions
  • 5.4 x 8.0 x 2.5 cm (2.1 x 3.1 x 1.0 in.) without base mounting flanges
  • 5.4 x 11.2 x 2.5 cm (2.1 x 4.5 x 1.0 in.) with base mounting flanges
Weight 92 g (3.2 oz)

Compatibility

Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.

Dataloggers

Product Compatible Note
CR1000 (retired)
CR1000X
CR200X (retired) To be compatible with the CR200X, the low-level ac signals must not exceed 1 kHz.
CR216X (retired) To be compatible with the CR216X, the low-level ac signals must not exceed 1 kHz.
CR300 (retired)
CR3000
CR310
CR350
CR5000 (retired)
CR6
CR800 (retired)
CR850 (retired)
CR9000X (retired) It is necessary to use the CR9071E module with the CR9000X and LLAC4.

Sensors

Product Compatible Note
014A
03002
034B
05103
05103-45-L (retired)
05106
05305-L

Additional Compatibility Information

Data Logger Considerations

The LLAC4 works only with data loggers whose control ports can accept high frequency pulses. The CR23X has four control ports that can be used (5, 6, 7, and 8); the CR200X-series control ports are compatible but are limited to inputs of 1 kHz.

Sensors

The LLAC4 typically measures anemometers. Compatible anemometers include the Wind Monitors, 03002 Wind Sentry Set, and 03101 Wind Sentry Anemometer. (The 014A Anemometer and 034B Windset are not compatible.) The LLAC4 can also measure other sensors that output pulse counting signals.

Downloads

LLAC4 Program Example (2 KB) 21-05-2024

Description: Includes two programs, one for a CR1000X and one for a CR350. Both programs measure three different wind speed sensors that produce low-level AC signals. The sensors used are the RM Young 05103 and RM Young 05305 propeller-type anemometers, as well as the RM Young 03101 cup anemometer.


FAQs for

Number of FAQs related to LLAC4: 1

  1. No. But using a LLAC4 will convert the ac signal for up to four 03101-L sensors (and other ac output anemometers) to individual 0 to 5 Vdc TTL level square wave outputs. For more information, see the LLAC4 specification information